Many control panels built in Europe are full of Moeller parts: DILM contactors, PKZM0 motor-protective circuit breakers, NZM moulded case circuit breakers and easy control relays. Eaton took over Moeller in 2008, and the same products now carry the Eaton name. For a buyer, one part can turn up under two brand names. This guide shows what to read off the failed part and what must match on the replacement.
One part, two names and two numbers
Every Moeller and Eaton part has a type designation, such as DILM12-10(24VDC), and a numeric article number. Both identify the same item. The type designation is printed on the device; the article number is on the label or the box. Write down both, and the brand as printed.
In North America the same IEC contactors and motor-protective circuit breakers are sold under XT catalogue numbers: XTCE for contactors, XTPR for motor-protective circuit breakers. A machine built there may carry an XT number while a European supplier lists the DILM or PKZM0 type. Ask the supplier to name the matching type in the quote before you order.
DILM contactors: size, auxiliary contact and coil
A DILM type designation has three parts. The table reads a common example.
| Part of the type | Example | What it tells you |
|---|---|---|
| Size | DILM12 | Rated operational current at AC-3 and 400 V: 12 A |
| Auxiliary contact | -10 | One normally open auxiliary contact; -01 is one normally closed |
| Coil voltage | (24VDC) | Control voltage and whether it is AC or DC |
Check the coil twice. A contactor with a 230 V AC coil will not pull in on a 24 V DC control circuit. Order the coil voltage exactly as printed in the brackets, together with the size and the auxiliary contacts. What the AC-3 and AC-1 ratings mean is explained in relay and contactor ratings.
PKZM0 and NZM breakers: setting range and breaking capacity
A PKZM0 motor-protective circuit breaker protects one motor. Its setting range must include the rated current on the motor nameplate, and the dial on the new breaker is set to that current. The short-circuit breaking capacity of the replacement must be at least that of the old breaker at your supply voltage. Auxiliary contacts and trip indicators clip onto the side; reuse them only if they belong to the same series.
NZM moulded case circuit breakers carry more in the type. In NZMN2-A160, the 2 is the frame size and the N is the breaking capacity class; the classes B, C, N and H rise in that order. The A marks system and cable protection, and 160 is the rated current in amperes. An M in place of the A marks a motor protection version. Match all four. A breaker with the same current but a lower class is not a replacement. The choice between breaker types is covered in replacing a circuit breaker.
easy control relays: from easy800 to easyE4
The easy500, easy700 and easy800 control relays have been followed by easyE4. Read the full type off the old device, for example EASY822-DC-TC: the letters after the number give the supply voltage and the output type. A used or new surplus device of the same type takes the old program and wiring without changes.
easyE4 is not a drop-in replacement. The program has to be moved to the new device in easySoft and tested, and the terminals and expansion modules differ. Before you order, find out whether the program is backed up, on a memory card or as a file, and who can load it.
What to send with a request for quotes
- The full type designation with the brackets, for example DILM12-10(24VDC).
- The numeric article number, if the label still shows it.
- The brand as printed: Moeller or Eaton.
- The condition you accept: new, new surplus, refurbished or used.
Search Sparehawk with the type designation or the article number, with or without spaces. If several parts on a panel failed, put them in one request for quotes (RFQ). It goes first to the best-matched suppliers for each line. Quotes come back into one comparison of price, lead time, condition and warranty. If nobody lists the part, post a wanted request and suppliers can answer it.