A relay or contactor usually fails in one of a few ways: a burnt coil, welded contacts or a cracked housing. The replacement is cheap, but only if the ratings match. This glossary covers the terms printed on the old part and what each one means for the new one.
What to read off the old part
Before you remove it, photograph the rating plate and the terminal side. Then note down:
- the full part number, including any suffix after the base type
- the coil voltage and whether it is AC, DC or both
- the rated current or power for each utilisation category printed
- the arrangement of the main and auxiliary contacts
- the mounting: DIN rail, screw fixing or plug-in socket
- any add-ons: auxiliary block, surge suppressor, overload relay or timer
The suffix often holds the coil voltage. Two contactors with the same base type and different suffixes are not interchangeable.
Coil voltage and supply
The coil connects to terminals A1 and A2. Common values are 24 V DC, 110 V AC and 230 V AC. The new coil must match both the voltage and the type of supply.
Some newer contactors have electronic coils that accept a voltage range and both AC and DC. They make a good replacement, but check that the range covers your control voltage.
A coil switched by a PLC output often needs a suppressor against voltage spikes. If the old part had a diode, varistor or RC module, order the same type for the new one.
Utilisation categories: AC-3, AC-15 and the rest
A contact rating means little without a load type. IEC 60947-4-1 defines categories for contactors, and IEC 60947-5-1 defines them for control relays and auxiliary contacts. The same contact can carry far more current to a heater than to a motor.
| Category | Load | Typical part |
|---|---|---|
| AC-1 | Resistive or slightly inductive loads, such as heaters | Contactor |
| AC-3 | Squirrel-cage motors: starting, switching off while running | Motor contactor |
| AC-4 | Squirrel-cage motors with inching or plugging | Motor contactor, derated |
| AC-15 | AC electromagnets, such as contactor and valve coils | Control relay, auxiliary contact |
| DC-13 | DC electromagnets, such as solenoid valves | Control relay, auxiliary contact |
Motor contactors are often listed by their AC-3 power in kW at 400 V. Compare that figure with the motor, not the AC-1 current. A relay good for 10 A at 250 V AC on a resistive load switches much less on a valve coil.
Contacts, auxiliaries and terminal markings
NO means normally open and NC normally closed. A changeover contact has both, with a common terminal. Many makers mark the auxiliary contacts with a code of two digits. The first digit is the number of NO contacts, the second the number of NC contacts. So 10 is one NO, and 11 is one NO plus one NC.
Terminal numbers follow the same logic on most contactors. The main contacts are 1/L1, 3/L2 and 5/L3 on the line side and 2/T1, 4/T2 and 6/T3 on the load side. Auxiliary NO contacts end in 3 and 4, such as 13 and 14. NC contacts end in 1 and 2, such as 21 and 22. If the new part keeps these markings, the existing wiring diagram still applies.
Relays and contactors in safety circuits
A contactor that stops a hazardous movement is part of a safety function. Its NC auxiliary contact often reports back to a safety relay. That only works with a mirror contact under IEC 60947-4-1, which stays open while any main contact is closed, even a welded one. A relay in such a circuit needs mechanically linked contacts under IEC 61810-3. Replace these parts like for like, or with a type the designer of the circuit has approved. The post on safety components explains why the choice is not free.
Ordering the replacement
Search Sparehawk by the full part number, with or without spaces. Where a number has been superseded, the current part and its predecessors are both shown. A contactor often fails together with the circuit breaker or overload relay in front of it. The circuit breaker guide covers what to match there.
If a panel needs several parts, list them in a bill of materials and send one request for quotes. It goes first to the suppliers best matched to each line. Each offer shows condition, country and lead time. For a coil or contact block, new surplus is usually a safe choice. For a used contactor, inspect the contacts before it goes back into a motor circuit.