A failed 24 V DC power supply stops every sensor, valve and PLC input it feeds, so the replacement is usually urgent. It is also one of the few parts where another brand often fits. What has to match is printed on the old unit. Read it before you search.
What to read off the old unit
| Rating | Typical marking | Rule for the replacement |
|---|---|---|
| Input | Single-phase 100 to 240 V AC or three-phase 400 to 500 V AC | Same supply type as the cabinet |
| Output voltage | 24 V DC, adjustable | Same, set to the old value |
| Rated output current | 5 A, 10 A or 20 A | Equal or higher |
| Approvals | CE, UL, Class 2 | Everything the machine needs |
Also copy the order number exactly as printed, with spaces and suffixes. Siemens SITOP order numbers start with 6EP. Phoenix Contact, Weidmüller and other makes print an order number on the device label as well.
Input and output: the values that must match
- Input. A single-phase supply takes 100 to 240 V AC. A three-phase one takes 400 to 500 V AC. Swapping one for the other means changing the cabinet wiring, not only the supply.
- Output voltage. Most 24 V supplies can be adjusted, often up to about 28 V. Check the setting on the old unit and set the new one the same. Long cable runs are sometimes compensated this way.
- Output current. Take the old rating or add up the loads. A 10 A supply delivers 240 W at 24 V. A higher rating is fine; a lower one is not.
Overload behaviour and reserve current
Two supplies with the same rating can behave differently when a load draws too much. Some hold a constant current. Others switch off and retry in short bursts, called hiccup mode. Hiccup mode can fail to start large capacitive loads, such as drives with a 24 V control input.
Many modern supplies also deliver a short reserve above the rated current. That reserve is what trips a miniature circuit breaker on the 24 V side when one branch shorts. If the old unit had it, the new one needs it too, or the breakers in the cabinet stop tripping selectively. For the breakers themselves, see replacing a failed circuit breaker.
Signals, redundancy and parallel operation
Check the terminals, not only the label. A wired DC OK contact tells the PLC that the output is present. If the new supply has no such contact, that input stays off and the machine may refuse to start.
Two supplies feeding one bus need a redundancy module or a parallel mode setting. When one unit of such a pair fails, replace it with the same type where you can, so both share the load evenly.
Approvals, space and heat
Control circuits on machines are usually built as PELV according to EN 60204-1. Machines shipped to North America may need UL approval or a Class 2 output. These marks are on the label; copy them into your request.
Measure the width on the DIN rail and the free space above and below the unit. Above about 60 °C ambient, many supplies reduce their output current, and some reach their full rating only when mounted upright. Note the terminal type as well, screw or push-in, so the wiring can be moved across without surprises.
Searching and requesting quotes
Search Sparehawk with the order number, with or without spaces. Where a number has been superseded, the current part and its predecessors are both shown. Each offer shows condition, country and lead time. If another brand is acceptable, send the ratings from the table above in one request for quotes and say which values are fixed. The guide on finding a replacement part covers the general steps.