A burnt or damaged breaker stops a panel as surely as a failed drive. The part itself is usually simple, but the spare has to match more than the current printed on the front. This article sorts out the three kinds you meet in machine panels and what to check for each.
Which kind of breaker failed
The kind decides which values matter. The shape and the label usually tell you.
| Kind | Product standard | How to recognise it |
|---|---|---|
| Miniature circuit breaker (MCB) | IEC 60898-1 | Rail-mounted, a narrow module per pole, curve and current on the front, such as C16 |
| Moulded case circuit breaker (MCCB) | IEC 60947-2 | Larger case, bolted or plug-in, frame size and trip unit on the label |
| Motor protection circuit breaker | IEC 60947-2 and IEC 60947-4-1 | Rotary knob or push buttons, setting range in amperes on a dial |
Many MCBs built into machines are also certified to IEC 60947-2. That does not change what you read off them.
What to read off the old breaker
Photograph the label and the front before you remove the part. Then note:
- The brand and the ordering code, exactly as printed, including any suffix.
- The rated current and, on an MCB, the trip curve letter: B, C or D.
- The number of poles, and whether the neutral is switched.
- The rated breaking capacity in kA: Icn on an MCB, Icu and Ics on an MCCB.
- The rated voltage, and whether the breaker is marked for AC, DC or both.
- Every accessory fitted: auxiliary contacts, a shunt trip, an undervoltage release, a rotary handle or a motor operator.
On an MCCB with an electronic trip unit, also write down the dial settings. They are part of the protection design and are lost when the unit is swapped.
What must match on the spare
Rated current, trip curve and number of poles must match the original. The curve sets how the breaker reacts to inrush current, so a C curve is no stand-in for a D curve on a transformer or motor circuit.
Breaking capacity must be equal to or higher than the original. A lower value can look fine on paper and fail at the one fault that matters.
AC and DC are not interchangeable. A breaker marked only for AC must not replace a DC breaker. Some DC breakers are polarity sensitive, so note which terminal was connected to which side.
On a motor protection circuit breaker, the rated current of the motor must sit inside the setting range of the spare. If the breaker works with a contactor in a tested combination, check the coordination table of the manufacturer before you change brand or series.
Mounting must fit as well: the same rail, bolt pattern, busbar or comb connection, and for an MCCB the same door cut-out for the handle.
When the series is discontinued
MCBs are the easiest case. A current model from the same brand or another one usually fits, provided rating, curve, poles and breaking capacity match. Check that the busbar comb still fits the new pitch.
MCCBs and motor protection breakers are harder. A successor frame often has other dimensions, other terminals and its own accessories. Siemens, for example, moved its moulded case range from 3VL to 3VA, and the accessories of the old range do not fit the new one. Manufacturers publish replacement tables for such moves. The obsolescence guide explains how to plan them before the next failure.
How to search and request quotes
Search the ordering code on Sparehawk, with or without spaces. Where a number has been superseded, the current part and its predecessors are both shown. Each offer shows condition, country and lead time, and the price where the supplier publishes it.
A fault rarely takes out only one breaker. Put every affected breaker and its accessories in one request for quotes. It goes first to the best-matched suppliers for each line, and the quotes come back into one comparison. If the code finds nothing, work through the checks for an empty search, or post a wanted request with the photo of the label.