A pressure sensor that fails on a hydraulic unit, a compressor or a filling line usually stops the machine with it. The quickest fix is the same part number. When that is not available, the replacement has to match on more points than the thread and the plug.
What to read off the old sensor
Before you remove the old unit, photograph the label and note the following:
- the full part number and the manufacturer, including any suffix after the base model
- the pressure range and its unit, in bar, psi or MPa
- whether the range is gauge, absolute or sealed gauge
- the output signal and the supply voltage
- the electrical connector and the thread on the process side
The suffix often carries the range, the output and the connection. Two sensors with the same model name can differ on all three.
Pressure range and reference
Gauge sensors measure against the surrounding air, so they read zero when the line is open. Absolute sensors measure against a vacuum and read about 1 bar at the same moment. Sealed gauge sensors use a fixed reference sealed inside the housing. Swapping one type for another shifts every reading by roughly one atmosphere, and a control loop will not notice that on its own.
Match the range to the scaling in the controller. If the old sensor read 0 to 10 bar and the new one reads 0 to 16 bar, the controller must be rescaled or every value will be wrong. Check the overpressure rating as well, especially on hydraulics, where pressure peaks can exceed the working range.
Output signal and wiring
Common outputs are 4–20 mA current, 0–10 V voltage, ratiometric voltage and digital interfaces such as IO-Link. A current sensor is usually two-wire and powered from the loop. A voltage sensor is usually three-wire. The analogue input card decides what fits, and a current input will not read a voltage sensor correctly. An IO-Link sensor also needs the right device description in the master configuration.
Many sensors combine a switching output with an analogue one on the same connector. Compare the pin assignment in both data sheets, not only the connector type.
Connector and process connection
Common electrical connections are an M12 plug, a DIN EN 175301-803 valve plug or a fixed cable. On the process side, G1/4 and 1/4 NPT look alike but do not interchange. G threads are parallel and seal on a gasket. NPT threads are tapered and seal on the thread itself. Forcing one into the other damages the port.
The wetted parts must suit the medium. Stainless steel suits most oils, water and compressed air. Aggressive media, refrigerants and food or pharmaceutical processes can need other diaphragm materials, other seals or a flush diaphragm. The housing must also suit its location, and the article on IP ratings on replacement parts explains the codes.
Approvals that must carry over
Some approvals cannot be dropped on a replacement. A sensor in a hazardous area needs a suitable ATEX or IECEx marking. Sensors on rolling stock are often required to meet EN 50155. Refrigeration, food and pressure equipment can have approvals of their own. If the old sensor carried one of these, the new one must carry it too, and the label is the first place to check.
Searching and requesting quotes
On Sparehawk, search takes the full part number with or without spaces. Where a number has been superseded, the current part and its predecessors are both shown. One request for quotes covers several sensors or a whole bill of materials for a machine. Write the range, reference, output, connector and thread into the request, so suppliers can quote an alternative when the original is not available. The guide on how to find a replacement part walks through the steps, and you can start a request for quotes with the part number alone.