Replacing a pressure sensor: what must match on the new one

A failed pressure sensor or transmitter is easy to replace with the wrong one. Read the range, reference, output, thread and approvals off the old unit before you search.
Author
Sparehawk
Reading time
4 min read
Published
  • Maintenance
  • Sourcing
  • Part numbers

A replacement pressure sensor must match the old one on six points: pressure range, pressure reference (gauge, absolute or sealed gauge), output signal, electrical connector, process connection and any approvals the machine needs. The wetted materials must also suit the medium. Read all of this off the label and the data sheet before you order. A sensor that fits the thread but reads the wrong range gives wrong values without raising an alarm.

A pressure sensor that fails on a hydraulic unit, a compressor or a filling line usually stops the machine with it. The quickest fix is the same part number. When that is not available, the replacement has to match on more points than the thread and the plug.

What to read off the old sensor

Before you remove the old unit, photograph the label and note the following:

  • the full part number and the manufacturer, including any suffix after the base model
  • the pressure range and its unit, in bar, psi or MPa
  • whether the range is gauge, absolute or sealed gauge
  • the output signal and the supply voltage
  • the electrical connector and the thread on the process side

The suffix often carries the range, the output and the connection. Two sensors with the same model name can differ on all three.

Pressure range and reference

Gauge sensors measure against the surrounding air, so they read zero when the line is open. Absolute sensors measure against a vacuum and read about 1 bar at the same moment. Sealed gauge sensors use a fixed reference sealed inside the housing. Swapping one type for another shifts every reading by roughly one atmosphere, and a control loop will not notice that on its own.

Match the range to the scaling in the controller. If the old sensor read 0 to 10 bar and the new one reads 0 to 16 bar, the controller must be rescaled or every value will be wrong. Check the overpressure rating as well, especially on hydraulics, where pressure peaks can exceed the working range.

Output signal and wiring

Common outputs are 4–20 mA current, 0–10 V voltage, ratiometric voltage and digital interfaces such as IO-Link. A current sensor is usually two-wire and powered from the loop. A voltage sensor is usually three-wire. The analogue input card decides what fits, and a current input will not read a voltage sensor correctly. An IO-Link sensor also needs the right device description in the master configuration.

Many sensors combine a switching output with an analogue one on the same connector. Compare the pin assignment in both data sheets, not only the connector type.

Connector and process connection

Common electrical connections are an M12 plug, a DIN EN 175301-803 valve plug or a fixed cable. On the process side, G1/4 and 1/4 NPT look alike but do not interchange. G threads are parallel and seal on a gasket. NPT threads are tapered and seal on the thread itself. Forcing one into the other damages the port.

The wetted parts must suit the medium. Stainless steel suits most oils, water and compressed air. Aggressive media, refrigerants and food or pharmaceutical processes can need other diaphragm materials, other seals or a flush diaphragm. The housing must also suit its location, and the article on IP ratings on replacement parts explains the codes.

Approvals that must carry over

Some approvals cannot be dropped on a replacement. A sensor in a hazardous area needs a suitable ATEX or IECEx marking. Sensors on rolling stock are often required to meet EN 50155. Refrigeration, food and pressure equipment can have approvals of their own. If the old sensor carried one of these, the new one must carry it too, and the label is the first place to check.

Searching and requesting quotes

On Sparehawk, search takes the full part number with or without spaces. Where a number has been superseded, the current part and its predecessors are both shown. One request for quotes covers several sensors or a whole bill of materials for a machine. Write the range, reference, output, connector and thread into the request, so suppliers can quote an alternative when the original is not available. The guide on how to find a replacement part walks through the steps, and you can start a request for quotes with the part number alone.

01

Frequently asked questions

1.1

Is a pressure switch the same as a pressure sensor?

No. A switch gives a contact or a digital signal at a set point, while a sensor or transmitter gives a continuous value. Some electronic pressure switches do both, so check which output the machine actually uses.
1.2

Can I fit a sensor with a wider pressure range?

Often yes, if the scaling in the controller is changed to the new range. Resolution and accuracy over the working range get worse, so do not go much wider than needed.
1.3

Should I buy a refurbished pressure sensor?

Sensors with a wetted diaphragm are rarely refurbished, so new or new surplus is the usual choice. If you take a used one, ask the supplier for the calibration date and a test report.
1.4

What if the label on the old sensor is unreadable?

Look for the part number in the machine documentation, the spare parts list or the hardware configuration of the controller. If nothing is left, post a wanted request with the thread, connector, output and operating pressure.